Description
一、Product Features
1. This product is specially designed for special communication and electronic equipment such as broadband network switches in occasions where overvoltage and lightning induction are frequent.
2. Mainly used for lightning (overvoltage) protection of low-voltage single-phase AC power supply (220V AC) system electronic and electrical equipment. Such as communication equipment, computer and network equipment, medical equipment, precision electronic equipment, household appliances, etc.
3. Equipped with international standard jacks, modular structure, simple and convenient installation.
4. The outer shell is made of high-quality imported flame-retardant materials, the plug-in components are phosphor bronze, and the products comply with international and national standards.
5. It has the functions of strong versatility, high mechanical strength, safe and reliable use and automatic overload protection.
6. The lightning protection component adopts the full protection mode of common mode and differential mode, and the selection of new technology and new technology is carefully developed.
7. The discharge current is large (10KA), the response time is fast (<25ns), and the indicator shows the component deterioration fault.
二、Technical Parameters
Product number | LFD-4P | LFD-6P | LFD-8P | LFD-10P |
product name | PDU Cabinet dedicated socket | |||
Shell material | Aluminum shell | |||
physical dimension | 19 inch standard cabinet | |||
Rated current | Main line(13A/16A) unit (10 A) | |||
Deterioration indicator | Indicator light | |||
Power connection specifications | 3*1.5mm*1.5 | |||
Rated working voltage Un | 220V 48/62 Hz | |||
Maximum continuous working voltage Uc | 255V 48/62 Hz | |||
Protection level Up(5Ka-8/20) | <1.2 Kv | |||
Nominal discharge current In(8/20) | 10 kA | |||
Maximum discharge current Imax(8/20) | 20 kA | |||
Reaction time tA | <25 ns | |||
Leakage current 1mA(75%U) | ≤20 μA | |||
Protection mode | Common mode(L、N/PE);Differential mode(L/N) | |||
Enclosure rating | IP20 | |||
range of working temperature | -40℃~+70℃ | |||
relative humidity | Under indoor temperature conditions 30%~90% | |||
Executive standard | GBl8802.1、lEC61643-1 |
三、Install the app
1. When the indicator light of the power switch button is pressed, the indicator light is on, it means the power is normally connected and the protector can be used normally; otherwise, it cannot be used.
2. When the lightning protection component failure indicator is on (red light), it indicates that the lightning protection component has failed; otherwise, it indicates that the lightning protection component is normal.
3. The load current of the protected equipment should be less than 10A, and it cannot be used with overload. If it is overloaded, the product will automatically disconnect the power; when it recovers, just press the red button at the inlet end of the power cord.
4. There is high voltage inside, please do not disassemble it by yourself.